Sikasil-670 Fire, Fire Rated Joint Sealant, Interior & Exterior
SIKA
Sika is a global leader in specialty chemicals for the construction and industrial sectors. The company develops and supplies innovative products and systems for bonding, sealing, damping, reinforcing, and protecting structures. With a strong focus on sustainability and performance, Sika serves a wide range of applications including concrete production, waterproofing, roofing, flooring, and structural strengthening.
Read more| FIRE RATED JOINT SEALANT Sikasil-670 Fire is a fire rated, 1-component, moisture-curing, low-modulus elastic joint sealant.
| ||||||||||||||||||||||||||||||||
UsageSikasil-670 Fire is designed for fire rated movement and connection joints on porous and non-porous substrates.Advantages
Packaging600 ml foil pack, 12 foil packs per box. 380 ml cartridge, 25 cartridges per box. 300 ml cartridge, 12 cartridges per box. ColourWhite, grey, black | ||||||||||||||||||||||||||||||||
Technical Information Shore A Hardness ~20 (after 28 d) (ISO 868) Secant Tensile Modulus ~0.30 N/mm2 at 100 % elongation (23 °C) (ISO 8339) Elastic Recovery ~70 % (ISO 7389) Tear Propagation Resistance ~4.0 N/mm (ISO 34) Movement Capability (ISO 9047) Service Temperature −40 °C min. / +150 °C max. Joint Design The joint width must be designed to suit the joint movement required and the movement capability of the sealant. The joint width shall be ≥ 10 mm and ≤ 40 mm. The joint depth shall be ≤ 20 mm. A width to depth ratio of 2:1 should be maintained (for exceptions, see table below). Standard joint widths for joints between concrete elements: Min. joint width [mm] Min. joint depth [mm] All joints must be correctly designed and dimensioned in accordance with the relevant standards, before their construction. The basis for calculation of the necessary joint widths are the type of structure and its dimensions, the technical values of the adjacent building materials and the joint sealing material, as well as the specific exposure of the building and the joints. For larger joints please contact our Sika Technical Service. | ||||||||||||||||||||||||||||||||
Application Information Backing Material Use polyethylene foam backing rods. Sag Flow
Ambient Air Temperature +5 °C min. / +40 °C max. Substrate Temperature +5 °C min. / +40 °C max., min. 3 °C above dew point temperature Curing Rate
Skin Time